SP121E Rev. 000 Siel S.p.A. Pag. 20 of 42
Issued date: 2005-05-06
GREEN POINT
ON - LINE
With the factory default setting, the UPS goes into ON LINE mode when switched on.
Display
message
Power
supply
SWIN FBY FBAT SWOUT SWMB Led
BATT
Led
IN
Led
OUT
Led
BY
Buzzer
NORMAL
OPERATION
ok on on on on off off on on off off
MAINS present and load powered.
The load is constantly supplied by the inverter with a stabilised and regulated voltage and frequency. If
a fault with the incoming mains supply occurs the UPS will instantaneously switch over to batteries,
which provide the power to the inverter and therefore maintains the power supply to the load. The
battery is then automatically recharged when the mains supply returns.
During either of these two operational conditions the inverter constantly supplies power to the load with
a stabilised and regulated voltage and frequency, ensuring that the load has a high degree of immunity
to disturbances etc, due to the double conversion. In the event of mains failure, no disruption in the
supply to the load will occur as the transfer is instantaneous.
STAND-BY ON
The STAND-BY ON mode and the by-pass line tolerance range must be set using the control panel.
The standby-on function reduces the energy dissipated by the system
Display message
Power
supply
SWIN FBY FBAT SWOUT SWMB
Led
BATT
Led
IN
Led
OUT
Led
BY
Buzz
er
NORMAL OPERATION
MODE STBY=ON
ok on on on on off off on on on off
The Converter remains active and the batteries are kept charged:
The switching time between the inverter and the by-pass line can be either set to immediately (Economy
Mode), or delayed up to a maximum of 180 minutes (Smart Active Mode). For the system to switch the
load onto the by-pass line, the bypass supply must be within the configured acceptable range for the
pre determined time set.
The system remains on the by-pass line for as long as the voltage and frequency fall within the
acceptable predetermined range. The input “IN” (green), output “OUT” (green), by-pass “BY”(yellow)
LEDs are permanently lit on the display panel.
During this operating mode, energy dissipated is significantly reduced (efficiency = 98%)
If the by-pass line fails or the voltage or frequency exceed the acceptable range, the load is
automatically switched onto the inverter output.