SP121E Rev. 000 Siel S.p.A. Pag. 22 of 42
Issued date: 2005-05-06
GREEN POINT
8 - INTERFACING
8.1 Remote signals and command connectors
The following connectors are situated on the rear. Refer to the “VIEWS OF THE UPS” section for details.
1 x EPO (emergency power off ) connection point;
1 x DB15 female REMOTE;
1 x DB9 male RS232-1;
1 x DB9 female RS232-2;
1 x Aux Slot for SNMP card etc.
8.2 EPO (Emergency Power Off command)
The EPO operates a normally closed system and by opening the link will force the UPS into an
emergency power off command.
Using this input, the UPS can be shut down remotely in the event of an emergency by pressing a single
emergency button. The EPO switches the UPS off which will remain in this state until reset.
8.3 DB15 Female “Remote”
This connector consists of:
1 x 12Vdc 80mA(max) power supply
3 x voltage-free alarm contacts
2 x Inverter and UPS shutdown commands
The pin layout is as follows ( see figure ):
BATTERY LOW = END OF DISCHARGE PRE-ALARM (the low battery
warning time can be configured )
BATTERY DISCHARGING = BATTERY DISCHARGING (mains failure)
BY-PASS / FAULT = BY-PASS/FAULT
The position of the contacts shown is during a non alarm state
(NORMAL OPERATION).
The contact rating is 42V @ 0.5A(max).
REMOTE COMMANDS
2 commands are available:
BYPASS with INVERTER STOP– by connecting pin 8 to pin 15 (for at least 2 seconds) used for external
bypass commands.
TOTAL STOP – by connecting pin 7 to pin 15 (for at least 2 seconds) the system will shut down.