GREEN POINT
10.2 Liquid Crystal Display ( LCD )
LCD display: status messages
During Normal Operation mode, where no specific information has been requested and/or no particular
command has been made using either the buttons on the control panel or via the RS232 remote line, the LCD
will display a number of basic messages.
It is possible to obtain further information, or perform commands, by accessing the sub-menus using buttons 1
– 8 of the control panel and following the instructions that appear on the screen.
10.3 List of the information output on the LCD display:
Selections
Help
Language selection (Italian – English – French – German - Spanish - Dutch - Swedish – Polish)
Measurements:
input voltage input frequency
input power by-pass voltage
by-pass frequency output voltage
output frequency output power
output peak power battery voltage
battery peak pulse current battery discharge current
inverter input voltage internal temperature (system/converter
/bypass/inverter/magnetic components)
inverter operation time by-pass operation time
battery operation time no. of battery interventions
no of complete discharges date of first activation
Commands
battery test display contrast
by-pass off end discharge pre-alarm
system off
Customisation
output voltage output voltage compensation
batteries line-interactive operating mode
end discharge pre-alarm auto off
by-pass voltage tolerance by-pass frequency tolerance
modem
Event Log
Enables the user to view up to 120 previous events . For each event, the measurements taken and alarms active
when the event occurred can also be seen.