SP121E Rev. 000 Siel S.p.A. Pag. 41 of 42
Issued date: 2005-05-06
GREEN POINT
MODEL 10000 15000 20000
INPUT
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Compliance with
safety regulations
EN62040-1
Directive 73/23/EEC and 93/68/EEC
EMC compliance EN50091-2 cl. A, directive 89/336/EEC
Immunity to sudden
current surges
6kV 300J in accordance with IEC61000-4-5
Noise <56dB(A)
DIMENSIONS
Height (mm) 1200
Width (mm) 450
Depth (mm) 750
Weight in Kg
(without integrated
batteries)
90 90 95 95 110 110
Max weight in Kg
(with integrated
batteries)
218 218 285 285 300 300
Mechanical
characteristics
Shielded metal cabinet with an applied plastic frontal display
Level of protection IP205
Resistance to
vibrations(G)
<2
Power dissipated
with load (W/Cal)
640/550 640/550 840/826 960/826 960/826 1280/1101
Power dissipated
no-load (W/Cal)
150/129 150/129 200/172 200/172 250/215 250/215
Ventilator range for
removing heat
320 mc/h 320 mc/h 480 mc/h 480 mc/h 480 mc/h 480 mc/h
Colour Light grey RAL7035
Input differential
current
<100mA
Protections
Thermal on system, rectifier, by-pass and inverter.
Protection against profound battery discharge.
Output protection figures (recommended values for selectivity)
Normal fuses (GI) In (rated current)/7
Normal circuit
breakers (curve C)
In (rated current)/7
Ultra-rapid fuses
(UR-URG)
In (rated current)/2
Cable input Front from rear
Input connections On terminals
Output connections On terminals
Cooling Forced variation varying with load and ambient temperature