GREEN POINT
MODEL 10000 15000 20000
INPUT
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Frequency
tolerance
configuration (from
the control panel)
±5% (1% steps)
Switching time
(mains to inverter
synchronised)
Null
Switching time
(mains to inverter
not synchronised)
Null
Switching time in
the Economy
/Smart Active mode
(by-pass to inverter)
<1ms
By-pass protection Fuse 50A/gR Fuse 50A/gR Fuse 63A/gG Fuse 63A/gG
Fuse
100A/gG
Fuse
100A/gG
Back-feed
protection
STANDARD
BY-PASS OVERLOADS (xIn)
1h 1.6 1.6 1.4 1.4 1.7 1.7
10’ 1.8 1.8 1.6 1.6 1.9 1.9
1’ 2.8 2.8 2.6 2.6 2.9 2.9
1s 5.1 5.1 5.4 5.4 7.4 7.4
10ms 20 20 20 20 28 28
Efficiency >99%
BATTERY
Back-up in mins
(factor 0.7) (internal
batteries)
From 0 to 17’
Back-up in mins
(factor 0.8)
(internal batteries)
From 0 to 15’
No batteries 32 32 48 48 48 48
Battery rated
voltage
384 384 576
Type of battery Sealed lead, high efficiency, maintenance-free
Battery
configuration
In series with mid point connection
Recharge current 4A minimum
Recharge time From 4 to 8 hours depending on back-up
Intervention time
(mains absent)
Null
Rated voltage on
expansion
connector
384V 384V 576V 576V 576V 576V
Rated output
supplied
8.9kW 8.9kW 11.7kW 13.3kW 13.3kW 17.8kW
Rapid recharge
voltage
442V 442V 662V 662V 662V 662V
Page view 37