6 - INSTALLATION INSTRUCTIONS
6.1 Electrical system requirements
6.1.1 Protections
UPS INTERNAL PROTECTION
The size of the circuit breakers and fuses positioned in the UPS input/output lines are shown in the table below
(refer to the block diagram section for an explanation of the abbreviations). Any fuse that requires replacement
must only be replaced with a fuse of the same type and rating, as indicated in the table below.
UPS with SINGLE-PHASE OUTPUT:
Switches and Internal Protections
UPS
Type
Non-automatic switches Fuses
[kVA]
UPS
Input
UPS Output /
Maintenance
Rectifier
Input Fuse
Battery Fuse Bypass Fuse
Input
Current
[A]
Output
Current
[A]
SWIN SWOUT/SWMB FBAT FBY Max Rated
10 63A (4P) 63A (2P) 20A gR(10x38) 30A gR(10x38) 50A gR(14x51) 51 43
15 100A (4P) 100A (2P) 30A gR(10x38) 30A gR(10x38) 63A gG(22x58) 67 65
20 100A (4P) 100A (2P) 30A gR(10x38) 30A gR(10x38) 100A gG(22x58) 74 87
UPS INPUT PROTECTION
When installing the UPS input protection devices, the maximum current drawn will be dependent on the
operational mode of the system when a fault occurs, therefore the following two operational modes must be
taken into account.:
During “NORMAL OPERATION”, the power to the load is supplied by the mains input via the
converter, and therefore the maximum input current drawn is that shown in the table above (under
the heading Input current max) .
During “BYPASS OPERATION, the power to the load is supplied directly via the by-pass line,
therefore the maximum input current drawn is limited by the rating of the bypass fuse shown in
table above (under the heading “Bypass fuse FBY).