SP121E Rev. 000 Siel S.p.A. Pag. 1 of 42
Issued date: 2005-05-06
GREEN POINT
TECHNICAL SPECIFICATIONS
10-15-20kVA single-phase / single-phase
10-15-20kVA three-phase / single-phase
GREEN POINT
Page view 0
1 2 3 4 5 6 ... 41 42

Summary of Contents

Page 1 - GREEN POINT

SP121E Rev. 000 Siel S.p.A. Pag. 1 of 42Issued date: 2005-05-06GREEN POINTTECHNICAL SPECIFICATIONS10-15-20kVA single-phase / single-phase10-15-20kVA t

Page 2 - Table of contents

SP121E Rev. 000 Siel S.p.A. Pag. 10 of 42Issued date: 2005-05-06GREEN POINT 5 - REFERENCE STANDARDS 5.1 Main reference standardsThe company qual

Page 3 - 1 - OBJECTIVE

SP121E Rev. 000 Siel S.p.A. Pag. 11 of 42Issued date: 2005-05-06GREEN POINTIEC61000-4-3:Immunity: electromagnetic fieldsIEC61000-4-4:Immunity: transie

Page 4 - 4 - CHARACTERISTICS

SP121E Rev. 000 Siel S.p.A. Pag. 12 of 42Issued date: 2005-05-06GREEN POINT5.2 Standards relating to systems and installationThe above product regulat

Page 5

SP121E Rev. 000 Siel S.p.A. Pag. 13 of 42Issued date: 2005-05-06GREEN POINT 6 - INSTALLATION INSTRUCTIONS6.1 Electrical system requirements

Page 6

SP121E Rev. 000 Siel S.p.A. Pag. 14 of 42Issued date: 2005-05-06GREEN POINTDifferential (Residual Current Device (RCD))In the standard version, where

Page 7

SP121E Rev. 000 Siel S.p.A. Pag. 15 of 42Issued date: 2005-05-06GREEN POINTL1 L2 L3 N NL PEL N NLINGRESSOINPUTUSCITAOUTPUTPE PEPECONNECTING THE SUPPLY

Page 8

SP121E Rev. 000 Siel S.p.A. Pag. 16 of 42Issued date: 2005-05-06GREEN POINTFBYSWINSWMBSWOUTInverterConverterInternal BatteryBatterie interneOutput 3Ph

Page 9

SP121E Rev. 000 Siel S.p.A. Pag. 17 of 42Issued date: 2005-05-06GREEN POINT 7.2 OptionsLEGEND :1) Automatic By-Pass:The automatic by-pass is an SCR (

Page 10 - 5 - REFERENCE STANDARDS

SP121E Rev. 000 Siel S.p.A. Pag. 18 of 42Issued date: 2005-05-06GREEN POINTemergency power off (EPO) as standard (see interface section)5) Slot for ne

Page 11 - Issued date: 2005-05-06

SP121E Rev. 000 Siel S.p.A. Pag. 19 of 42Issued date: 2005-05-06GREEN POINTThe static bypass can support overloads greater than those supported by the

Page 12

SP121E Rev. 000 Siel S.p.A. Pag. 2 of 42Issued date: 2005-05-06GREEN POINT Table of contents..1.. OBJECTIVE 3..2.. DESCRIPTION OF THE SYSTEM 3..

Page 13

SP121E Rev. 000 Siel S.p.A. Pag. 20 of 42Issued date: 2005-05-06GREEN POINTON - LINEWith the factory default setting, the UPS goes into ON LINE mode w

Page 14

SP121E Rev. 000 Siel S.p.A. Pag. 21 of 42Issued date: 2005-05-06GREEN POINTSTAND-BY FUNCTION:The UPS can be programmed to operate in stand-by mode. Du

Page 15

SP121E Rev. 000 Siel S.p.A. Pag. 22 of 42Issued date: 2005-05-06GREEN POINT 8 - INTERFACING8.1 Remote signals and command connectorsThe following

Page 16 - 7 - SYSTEM BLOCK DIAGRAM

SP121E Rev. 000 Siel S.p.A. Pag. 23 of 42Issued date: 2005-05-06GREEN POINT8.4 DB9 female “RS 232-1” PC connectionCan be used to connect the UPS to a

Page 17 - LEGEND :

SP121E Rev. 000 Siel S.p.A. Pag. 24 of 42Issued date: 2005-05-06GREEN POINT 9 - OPTIONS9.1 Summary table of the options availableDescriptionDimen

Page 18

SP121E Rev. 000 Siel S.p.A. Pag. 25 of 42Issued date: 2005-05-06GREEN POINT9.2 - Communication softwareMAIN CHARACTERISTICS1) Sequential and priorit

Page 19 - 7.3 Operating modes

SP121E Rev. 000 Siel S.p.A. Pag. 26 of 42Issued date: 2005-05-06GREEN POINTGreenshield is the easy to use yet powerful program that enables the user t

Page 20

SP121E Rev. 000 Siel S.p.A. Pag. 27 of 42Issued date: 2005-05-06GREEN POINT 10 - CONTROL / DISPLAY PANEL10.1. LED Panel Control / Display panel

Page 21

SP121E Rev. 000 Siel S.p.A. Pag. 28 of 42Issued date: 2005-05-06GREEN POINTLEDsThe LEDs can be either lit, flashing or off, thus providing immediate i

Page 22 - 8 - INTERFACING

SP121E Rev. 000 Siel S.p.A. Pag. 29 of 42Issued date: 2005-05-06GREEN POINT10.2 Liquid Crystal Display ( LCD )LCD display: status messagesDuring Norma

Page 23

SP121E Rev. 000 Siel S.p.A. Pag. 3 of 42Issued date: 2005-05-06GREEN POINT 1 - OBJECTIVEThis technical document has been produced to be used by UP

Page 24 - 9 - OPTIONS

SP121E Rev. 000 Siel S.p.A. Pag. 30 of 42Issued date: 2005-05-06GREEN POINT10.4 Alarm messagesThe alarm messages that appear on the first line of the

Page 25

SP121E Rev. 000 Siel S.p.A. Pag. 31 of 42Issued date: 2005-05-06GREEN POINTThis alarm is present if one of the following conditions occurs:− the inco

Page 26

SP121E Rev. 000 Siel S.p.A. Pag. 32 of 42Issued date: 2005-05-06GREEN POINTThis transitory phase occurs, for example, when the machine has just been s

Page 27 - 10.1. LED Panel

SP121E Rev. 000 Siel S.p.A. Pag. 33 of 42Issued date: 2005-05-06GREEN POINTThis alarm is present when the total shutdown command has been activated us

Page 28

SP121E Rev. 000 Siel S.p.A. Pag. 34 of 42Issued date: 2005-05-06GREEN POINTREARRETROEA BCDREAR VIEW (10÷20 kVA) 11 - VIEWS OF THE UPS11.1 Front a

Page 29

35GREEN POINT 12 - TECHNICAL DATA12.1 ModelsMODEL POWER BACK-UP cosfi 0.8 BACK-UP cosfi 0.7 DIMENSIONS (HWD) mm WEIGHT kg0 0 908 10 18011 13 20

Page 30 - 10.4 Alarm messages

SP121E Rev. 000 Siel S.p.A. Pag. 36 of 42Issued date: 2005-05-06GREEN POINT12.2 Back-up expansion modulesMODEL BACK-UP factor 0.8 BACK-UP factor 0.7 D

Page 31

37GREEN POINT12.3 Summary data sheets of models 10-20kVAMODEL 10000 15000 20000INPUTSingle-phaseinputThree-phaseinputSingle-phaseinputThree-phaseinp

Page 32

SP121E Rev. 000 Siel S.p.A. Pag. 38 of 42Issued date: 2005-05-06GREEN POINTMODEL 10000 15000 20000INPUTSingle-phaseinputThree-phaseinputSingle-phasein

Page 33

SP121E Rev. 000 Siel S.p.A. Pag. 39 of 42Issued date: 2005-05-06GREEN POINTMODEL 10000 15000 20000INPUTSingle-phaseinputThree-phaseinputSingle-phasein

Page 34 - 11 - VIEWS OF THE UPS

SP121E Rev. 000 Siel S.p.A. Pag. 4 of 42Issued date: 2005-05-06GREEN POINT 3 - APPLICATIONSPersonal computersSmall IT networksLocal Area Networks

Page 35 - 12 - TECHNICAL DATA

SP121E Rev. 000 Siel S.p.A. Pag. 40 of 42Issued date: 2005-05-06GREEN POINTMODEL 10000 15000 20000INPUTSingle-phaseinputThree-phaseinputSingle-phasein

Page 36

SP121E Rev. 000 Siel S.p.A. Pag. 41 of 42Issued date: 2005-05-06GREEN POINTMODEL 10000 15000 20000INPUTSingle-phaseinputThree-phaseinputSingle-phasein

Page 37

SP121E Rev. 000 Siel S.p.A. Pag. 42 of 42Issued date: 2005-05-06GREEN POINTMODEL 10000 15000 20000INPUTSingle-phaseinputThree-phaseinputSingle-phasein

Page 38

SP121E Rev. 000 Siel S.p.A. Pag. 5 of 42Issued date: 2005-05-06GREEN POINTThe parallel system modification does not require the UPS to be manually cal

Page 39

SP121E Rev. 000 Siel S.p.A. Pag. 6 of 42Issued date: 2005-05-06GREEN POINT(on-line). When the mains supply returns to within the acceptable limits, th

Page 40

SP121E Rev. 000 Siel S.p.A. Pag. 7 of 42Issued date: 2005-05-06GREEN POINTThe UPS can be configured to automatically restart after a mains supply fai

Page 41

SP121E Rev. 000 Siel S.p.A. Pag. 8 of 42Issued date: 2005-05-06GREEN POINTEasy to install and maintainSimplified installation:The UPS can be connected

Page 42

SP121E Rev. 000 Siel S.p.A. Pag. 9 of 42Issued date: 2005-05-06GREEN POINTThe software enables the user to programme the automatic start-up and shutdo