SP121E Rev. 000 Siel S.p.A. Pag. 15 of 42
Issued date: 2005-05-06
GREEN POINT
L1 L2 L3 N NL PE
L N NL
INGRESSO
INPUT
USCITA
OUTPUT
PE PE
PE
CONNECTING THE SUPPLY AND LOAD
UPS with single-phase output (three-phase + neutral input)
Refer to the table below for the recommended cross sectional area
of the input and output cables. The figures within the brackets are
the maximum sizes that may be connected to the system terminals.
Size. [mm²]
INPUT OUTPUT
kVA L1 L2/L3 N PE L1/N
10 10(50) 4(50) 10(50) 10(50) 10(50)
15 16(50) 6(50) 16(50) 16(50) 16(50)
20 25(50) 10(50) 25(50) 25(50) 25(50)
UPS with single-phase output (single-phase input)
To operate the UPS with a single-phase input, the jumper (supplied) must be fitted across the three live input
terminals (L1, L2, and L3) as shown below.
Refer to the table below for the recommended cross sectional area of the input and output cables. The figures
within the brackets are the maximum sizes that may be connected to the system terminals.
Size. [mm²]
INPUT OUTPUT
kVA L1 N PE L1/N
10 10(50) 10(50) 10(50) 10(50)
15 16(50) 16(50) 16(50) 16(50)
20 25(50) 25(50) 16(50) 25(50)
L1 L2 L3 N NL PE
L1 L2 L3 N NL
INGRESSO
INPUT
USCITA
OUTPUT
PE PE
PE