SP121E Rev. 000 Siel S.p.A. Pag. 31 of 42
Issued date: 2005-05-06
GREEN POINT
This alarm is present if one of the following conditions occurs:
the incoming mains supply voltage is insufficient.
the output load, measured in active power [W], exceeds the rated value.
[8] OUTPUT OVERLOAD
Indicates that the power drawn by the load and provided by the inverter exceeds the permitted value. The value
indicated, expressed in %VA, exceeds 100%.
This alarm is activated whenever the peak current absorbed by the load exceeds the maximum value permitted.
When this alarm occurs the load should be reduced immediately. Otherwise the system will switch the load onto
the by-pass line, with a time delay inversely proportional to the size of the overload.
[9] BY-PASS FOR VA OUTPUT < AUTO-OFF VALUE
This alarm is activated whenever the power measured in %VA drawn by the load is less than the "AUTO-OFF"
value that has been set.
The %VA AUTO-OFF value is set to zero by the manufacturer (thereby disabling this alarm).
[10] INTERNAL FAULT: number
The various faults indicated are:
INTERNAL FAULT 1 - Precharge circuit fault
INTERNAL FAULT 2 - Inverter
INTERNAL FAULT 3 - Inverter output contactor failure
INTERNAL FAULT 4 - Booster output voltage
INTERNAL FAULT 5 - SCR on bypass line
INTERNAL FAULT 6 - Input contactor failure
INTERNAL FAULT 7 - Internal power supply error on the control board
INTERNAL FAULT 8 - Battery charger high voltage
INTERNAL FAULT 9 - SCR battery
INTERNAL FAULT 10 - Fault on parallel signal circuits
INTERNAL FAULT 11 - Switching on inverter failure
INTERNAL FAULT 20 - DC output voltage failure
INTERNAL FAULT 21 - A UPS operating as slave has distorted current flow
INTERNAL FAULT 22 - Parallel slave UPS has a different software version
INTERNAL FAULT 23 - Parallel UPS with different number of output phases
INTERNAL FAULT 24 - Transmission error from parallel master UPS
INTERNAL FAULT 25 - UPS previously activated in parallel mode
INTERNAL FAULT 26 - Switch over to bypass line failed
INTERNAL FAULT 27 - Failure on bypass SCR power supply
INTERNAL FAULT 28 - Input circuit with active filter failure
INTERNAL FAULT 29 - Active filter communication failure
INTERNAL FAULT 30 - Failure on temperature sensor
INTERNAL FAULT 31 - Microprocessor failure
[11] TEMPORARY BY-PASS, WAIT
Indicates that the load is powered by the by-pass line and that the system is about to automatically return to
normal operation, where the load is powered by the inverter.