GREEN POINT
12.3 Summary data sheets of models 10-20kVA
MODEL 10000 15000 20000
INPUT
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Input phases
1 (single or
three-phase
input
selectable on
site)
3 (single or
three-phase
input
selectable on
site)
1 (single or
three-phase
input
selectable on
site)
3 (single or
three-phase
input
selectable on
site)
1 (single or
three-phase
input
selectable on
site)
3 (single or
three-phase
input
selectable on
site)
Rated voltage
220-230-
240V
380-400-
415V
220-230-
240V
380-400-
415V
220-230-
240V
380-400-
415V
Maximum input
voltage before
battery intervention
276V 480V 276V 480V 276V 480V
Minimum input
voltage before
battery intervention
(applied load 100%)
184V 320V 184V 320V 184V 320V
Rated frequency 50/60Hz with auto sensing
Maximum current 51 18 67 26 74 35
Rated current 39 13 59 20 78 26
In-rush current <In
Power factor 0.99 0.95 0.99 0.95 0.99 0.95
Current distortion
(THDi)
<7% <27% <7% <27% <7% <27%
“Hold up” time
(acceptable mains
supply interruption
before battery
intervention)
20 ms
BY-PASS
Maximum voltage
acceptable for
switching to mains
+15%
Minimum voltage
acceptable for
switching to mains
-15%
Voltage tolerance
configuration (from
the control panel)
From ±5% to ±25% (5% steps)
Rated current 43A 43A 65A 65A 87A 87A
Maximum frequency
tolerance accepted
for switching to
mains
+5%
Minimum frequency
tolerance accepted
for switching to
mains
-5%