Siel Green Point 6:20KVA Specifications Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 42
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
SP121E Rev. 000 Siel S.p.A. Pag. 40 of 42
Issued date: 2005-05-06
GREEN POINT
MODEL 10000 15000 20000
INPUT
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Single-phase
input
Three-phase
input
Output frequency
variation with mains
present
2% (selectable)
Output frequency
variation (from
display panel)
From 1 to 5%
Frequency variation
velocity (Hz/sec.)
2 Hz/sec
Voltage reset after
dynamic variation
<10ms
Voltage distortion
(linear load)
<2%
Voltage distortion
(non-linear load)
<5%
OVERLOAD
100%<Load<110% 5h
110%<Load<125% 10’
125%<Load<150% 1’
Short circuit current
(t<0.5 sec.)
3In
Short circuit current
(phase/neutral)
3In
Inverter efficiency 94% 94% 94% 94% 94% 94%
VARIOUS
AC/AC efficiency
(double conversion
function)
92%
AC/AC efficiency
(Line interactive
function)
98%
Maximum
permanent
operating
temperature
40°C
Ambient operating
temperature
40°C
Recommended
operating
temperature (for the
batteries)
20/25°C
Humidity
95% without condensation
Maximum altitude
for installation
1000m
Derating for
altitudes above the
rated value
-1%Pn every 100m above 1000m
Page view 39
1 2 ... 35 36 37 38 39 40 41 42

Comments to this Manuals